Conventional heat detectors TS/TR
Main characteristics
Static / Elevation of T°
Lockable
Standard EN54-5
1 remote alarm indicator output
Cable section max 2,5mm²
- Function
- Specifications
- Description
- Additional information
- Reviews (0)
Main characteristics
Static / Elevation of T°
Lockable
Standard EN54-5
1 remote alarm indicator output
Cable section max 2,5mm²
Power supply specification
Main supply voltage: 13V to 27Vdc
Nominal main supply voltage 20Vdc
Quiescent current 20-30µA
Alarm current: 32ma
Mechanical characteristics
Unit weight: 130g
Unit dimensions (in mm): H:55, D:104
Unit row material: ABS
Unit colour: White
Protection class: IP32
Climatic characteristics
Operating temperature: -10°C to +50°C
Storage temperature: +10°C to +50°C
Operating relative humidity: ≤ 93%
Storage relative humidity: ≤ 85%
Description
Both Temperature heat detectors analyze the ambient temperature by the means of thermistor type CTN.
TSC05 (static heat detector) is either classified A1S or BS according to EN54-5 standard:
TSC05-A1S: static T°=62°C±3°C
TSC05-BS: static T°=75°C±5°C
TRC05 (static + rate of rise detector) is especially adapted for average ambient temperature conditions
under +10°C. TRC05 is classified A1R according to EN54-5 standard:
Static T°=62°C±3°C
ΔT°>9°C/min
Both types include a developed technology (microprocessors, smd components) which means precision
and high reliability. A specific head detection fixed by a single ceiling base.
12V version of TRC05 & TSC05 detectors is also available for security type systems
Additional information
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 in |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Be the first to review “Conventional heat detectors TS/TR” Cancel reply
Related Products
-
0 out of 5
Conventional Smoke Detector GFE-C
Key Features
- Dual LEDs for 360º visibility
- Advanced detection and communication protocols
- Easy installation and maintenance
- Sleek low-profile housing
- Durable sensor head, no need for replacement
- SMD circuit board design. High quality and reliability guaranteed
- Sensor Base Option: Regular GFE Detector Base or Deep Base
-
0 out of 5
Conventional MCP GFE-MCPE
GFE-MCPE
Conventional Manual Call PointThe GFE-MCPE-C is a Conventional Manual Call Point, designed and manufactured to comply with EN54-11,
compatible with all GFE Conventional Control panels. A bi-colour LED flashes Green when the unit is connected to a
control panel and is illuminated Red when in Alarm.
The unit is supplied complete with a hinged flap which protects the trigger element from accidental activation and
reduces malicious activations as two actions are required in order to activate the device. This unit can be both
surface and flush mounted and it can be easily reset using the supplied key after activation. -
0 out of 5
Honeywell Gent Conventional Smoke Detector : Eco 1003
F E A T U R E S
- Photo-thermal model
- Laser-based remote test unit
- EN 54 Certified (2000 edition)
- Photoelectric, photo-thermal and thermal detectors
- Improved chamber design
- Compatible with fire and security systems
- -20 to +60ºC operating temperature range
- Choice of bases (including a 12V relay version)
- Photoelectric model with integral piezoelectric sounder
(availability subject to further announcement)
-
0 out of 5
Global Fire Conventional Panel ORION 2-4-8
- 2, 4 and 8 Zone non-expandable control panels
- Up to 32 conventional smoke and/or heat detectors per Zone
- Active End of Line monitoring
- Programmable non-latching Zones
- Delay timer programmable on/off per Zone
- Coincidence programmable for adjacent Zones
- One man test
- Supervised auxiliary 24 volt output
- 2 Supervised/ monitored sounder circuits
- 3 Remote inputs used for activation of Class Change, Day/Night mode, and Reset
- 2 Relay outputs fire and fault
- Fully EN54 part 2 and 4 compliant
- Repeater output
- Multiplexed output for LEDs and additional relay outputs per zone (GFE-MPX-REL)
- Multiplexed output for sounders per zone (GFE-MPX-SNDR)
- Addressable Loop Interface card (GFE-ADLI)
- 2 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 2
- 4 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 4
- 8 ZONES CONVENTIONAL FIRE DETECTION CONTROL PANEL: ORION 8
-
0 out of 5
ALPHA 4/8/12 Conventional fire detection panel
Main features
From 4 (128 points) to 12 (384 points) conventional
detection lines
2 Extinguishing zones manageable
32 detectors and/or MCP each line
Monitored sounders line
Day/night mode
Keyboard programmable ad access level 3
Easy management
Reviews
There are no reviews yet.